Once the transient model has fixed the gas duty, the vessel type looks like a procurement detail. It is not. On this series' reference main the duty is 3.08 m³ of gas at the steady HGL, expanding to 15.30 m³. An air-over-water vessel carries that in a 19.1 m³ shell; a bladder vessel pre-charged below the minimum pressure needs 23.2–28.4 m³ at any pre-charge from atmospheric up to 0.95 of the minimum. The bladder saves a compressor and dissolved-air losses. You pay in shell volume, a membrane that wears, and pre-charge checks that need the vessel out of service.

1 · Same duty, three machines

When the pumps trip, a vessel's compressed gas pushes water into the line until the column turns, then takes the returning water back. The duty is a statement about gas, not steel: how much gas sits in the vessel at the steady hydraulic grade line, and how far it may expand before the pressure reaches the design minimum [1]. That is the same whichever vessel carries it. What changes is the shell, what keeps the gas there between trips, and what fails.

The reference system is a 12 km DN800 ductile iron K9 main [2]: 2,520 m³/h (1.39 m/s), wave speed 1,050 m/s, 85.0 m at the pump, 44.8 m at the delivery reservoir, PN16 with 136 m allowable, and a +3.0 m minimum anywhere. With all pumps tripped and no protection, the line reaches vapour and the collapse peak is 165–190 m. A vessel at the pump with a free DN400 connection (K 0.5) holds +3.0 m with 3.08 m³ of gas at 95.33 m abs (9.35 bar abs), expanding to 15.30 m³. With a 20 % water reserve at maximum expansion, the air-over-water shell is 15.30/0.8 = 19.1 m³. The sizing method is in Sizing the Hydropneumatic Surge Vessel; this article starts where it ends.

Where the numbers come from A method-of-characteristics model with a vapour cavity model, cross-checked with a gas cavity model and an independent second code. These are not HAMMER results; a project analysis must be run in HAMMER, or an equivalent, on the real profile. Collapse peaks are ranges because the spike when a cavity closes depends on how the cavity is represented [3]; on this series' cases the gas cavity model puts collapse peaks between 18 % lower and 10 % higher than the vapour cavity model. Never design on a collapse peak: protect the downsurge so no cavity forms. Vessel duties and protected minima involve no cavitation and are quoted to 0.1 m or 0.01 m³.

2 · How each type holds its gas

Air-over-water

A pressure vessel partly filled with water, with compressed air above a free surface. Nothing separates gas from water, so the gas volume is whatever the level says it is. It needs a level transmitter, a compressor to add air, a vent to release it, and controls to hold the level in a band. Air dissolves under pressure, so top-up continues for as long as the vessel is in service [4], [5].

Bladder

A flexible bladder separates gas from water. Before any water enters, the gas side is charged to a pre-charge pressure and fills the whole shell. As the line comes up to pressure the bladder is squeezed into a fraction of the shell set by the ratio of pre-charge to steady pressure. No compressor, no level control, no dissolved-air loss — but the gas volume now rests on a pressure you set once, cannot see in service, and must check [5], [6].

Diaphragm

The same physics, with a membrane fixed across the shell instead of a bag. Diaphragm vessels are typically chosen for smaller volumes; everything said below about pre-charge applies to them too.

One identity ties the three together. The duty fixes a mass of gas: 3.08 m³ at 95.33 m abs is 3.08 × 95.33/10.33 = 28.4 m³ of free air. An air-over-water vessel stores it compressed, put there by a compressor. A bladder vessel pre-charged at atmospheric pressure needs a shell of exactly 28.4 m³, because the shell is the container that free air is sealed into before it is squeezed. A higher pre-charge shrinks the shell in proportion; the next section is about how high it can go.

3 · The pre-charge penalty

Between trips a bladder vessel's gas sits at ambient temperature, however quickly the line came up to pressure, so the steady state lies on the isotherm through the pre-charge. The expansion on a trip is faster (on the reference duty the gas reaches its largest volume about 46 s after the trip), so design uses a polytropic exponent n = 1.2 between the isothermal and adiabatic limits [1], [4]:

\[ V_{shell} = V_0\,\frac{P_0}{P_{pre}}, \qquad V_{min} = V_0\left(\frac{P_0}{P_{min}}\right)^{1/n}, \qquad V_{shell,\,AOW} = \frac{V_{min}}{1-r} \]

All pressures are absolute: \(V_0\) is the gas at the steady pressure \(P_0\) = 95.33 m abs, \(P_{min}\) = 3.0 + 10.33 = 13.33 m abs, \(P_{pre}\) the pre-charge and \(r\) the air-over-water reserve. The pre-charge must stay below the lowest pressure the vessel will see, or the bladder is fully expanded, and delivering nothing, before the line reaches its minimum. Write \(P_{pre} = f\,P_{min}\) and divide the two shells:

\[ \frac{V_{shell,\,bladder}}{V_{shell,\,AOW}} = \frac{1-r}{f}\left(\frac{P_0}{P_{min}}\right)^{1-1/n} \]

The gas volume drops out. The penalty grows with the pressure ratio, so a high-head main protected to a low minimum is the worst case for a bladder: its shell is set by isothermal charging, the air-over-water shell by the smaller polytropic expansion. Here 7.15 to the power 1/6 is 1.39, so even pre-charged at the minimum itself the bladder shell is 39 % larger than the gas at the minimum. That extra is water the bladder keeps, doing the job of the air-over-water reserve: against the air-over-water shell the penalty at f = 1 is 11 %, and the pre-charge margin adds the rest, to 23 % at f = 0.90. Simplified methods give the first estimate of an air vessel [7]; the transient model is the check.

Shell volume for the reference duty: 3.08 m³ of gas at 95.33 m abs, minimum 13.33 m abs, n = 1.2. Air-over-water row from the transient model; bladder rows from the closed form
Vessel and pre-chargePre-charge (m abs)Pre-charge (m gauge)Shell (m³)Gas at the minimum (m³)Water left at the minimum (m³)Shell vs air-over-water
Air-over-water, 20 % reserve (transient model)––19.115.303.8–
Bladder, 0.60 × Pmin8.00−2.3336.715.920.8+92 %
Bladder, atmospheric (0.775 × Pmin)10.330.0028.415.912.6+49 %
Bladder, 0.80 × Pmin10.66+0.3327.515.911.7+44 %
Bladder, 0.90 × Pmin12.00+1.6724.515.98.6+28 %
Bladder, 0.95 × Pmin12.66+2.3323.215.97.3+21 %

The bladder rows use the closed-form 15.9 m³ at the minimum, slightly above the transient model's 15.30 m³: the closed form assumes the vessel itself is drawn down to +3.0 m, while in the model the line minimum occurs 4.6 km out and the vessel bottoms at 13.9 m abs (+3.6 m). The shells follow from the 3.08 m³ and the pre-charge alone, and in the transient model the 24.5 m³ bladder vessel gives exactly the air-over-water result, +3.0 m minimum and 130.9 m maximum, because the bladder never reaches the shell wall.

Now the gauge column. Every pre-charge that meets the rule and can be set by ordinary charging lies between atmospheric (f = 0.775, the 28.4 m³ free-air shell) and 0.29 bar g. The 0.60 row would need a vacuum, so with at least a 5 % margin the practical shells run from 23.2 to 28.4 m³, on a pre-charge that has to be exactly right. A transient study of one bladder shell at different pre-charges is in Pre-Charge Pressure.

4 · Interactive: shell volume by vessel type

Each bar shows what fills the shell at the lowest pressure: expanded gas, and the water still inside. The gas at the minimum is the closed form, so at the reference duty the air-over-water shell reads 19.8 m³ rather than the transient model's 19.1 m³, which is drawn dashed while the gas, HGL, minimum and exponent sit at the reference values. The transient model's own output is the 15.30 m³ of gas at maximum expansion, so that dashed line follows the reserve slider too: it is 15.30/(1 − reserve).

Shell volume for the same gas duty: air-over-water vs bladder or diaphragm
Gas at the minimum from polytropic expansion. Bladder shell from isothermal charging to the steady HGL. Air-over-water shell = gas at the minimum / (1 − reserve). Pressures absolute, atmosphere 10.33 m. Dashed line: the transient model's 15.30 m³ of gas at maximum expansion divided by (1 − reserve), so it moves with the reserve slider; shown only at the reference duty.
From the transient model. 3.08 m³ is the reference duty with a free DN400 connection.
Gauge head at the vessel in normal pumping. Sets P0 = HGL + 10.33 m.
The design minimum, gauge. The vessel is assumed to be drawn down to it.
1.0 isothermal, 1.4 adiabatic. 1.2 is the usual design value for a trip.
On absolute pressure. The margin below 1.0 is engineering judgement.
Water left at maximum expansion, so air never reaches the outlet.
Gas at the minimum
15.9 m³
Air-over-water shell
19.8 m³
Bladder shell
24.5 m³
Bladder penalty
+23 %
Pre-charge
12.00 m abs (+1.67 m g)

At the reference duty the bladder shell is 24.5 m³ against 19.8 m³: 23 % larger on the same closed-form basis, and 28 % larger than the transient model's 19.1 m³. The reserves differ, though: at the minimum the bladder shell is still 35 % water, against 20 %. Push the pre-charge to 0.98 and the gap only narrows to 13 %; drop it to 0.60 and the bladder shell is 85 % larger than the air-over-water shell. Now change the system instead. Raise the steady HGL to 200 m and the penalty grows to 41 %. Bring it down to 30 m with a +20 m minimum, a low-lift main, and the bladder becomes the smaller vessel by 7 %. The pressure ratio settles part of the type decision before anyone opens a catalogue.

5 · Interactive: the gas path

The same comparison, drawn as the gas sees it. Both axes are logarithmic, so the isothermal charge is a straight line of slope −1 and the polytropic expansion a steeper one of slope −n.

Gas pressure and volume through charging and a pump trip
Reference duty: 3.08 m³ at 95.33 m abs, design minimum 13.33 m abs. Bladder: the pre-charge fills the shell, charging to the steady HGL is isothermal, the trip expansion is polytropic. Air-over-water: the compressor charges 3.08 m³ directly, shell with a 20 % reserve. Grey dashed: expansion beyond the design minimum until the gas fills the shell.
The hydraulic duty is identical. Only the way the gas gets there changes.
Bladder and diaphragm only. Below 0.775 the pre-charge is below atmospheric.
Set 1.0 to see a slow, isothermal drawdown.
Pre-charge
12.00 m abs · +0.16 bar g
Shell
24.5 m³
Gas at the steady HGL
12.6 % of shell
Gas at the minimum
15.9 m³
Gas fills the shell at
7.9 m abs

The 12.00 m abs pre-charge fills 24.5 m³; charging squeezes it along the isotherm into 12.6 % of the shell; the trip expands it along the polytrope to 15.9 m³ at the minimum. Everything to the right of that point is shell you paid for and do not use. The dashed segment shows a fast expansion would have to reach 7.9 m abs before the gas filled the bladder shell; for air-over-water it ends at 10.2 m abs, where the reserve runs out. Do not count on that bladder margin. Set the exponent to 1.0 and the bladder reaches the wall exactly at the pre-charge, because in a slow drawdown the gas stays at ambient temperature — which is why we judge the pre-charge on the isothermal case, the conservative one.

6 · Air-over-water: compressors, level control and dissolved air

An air-over-water vessel is a pressure vessel plus a small process plant, and the type decision is really about the plant:

The level set points are not a controls detail; they are the surge protection. On the site's reference vessel — 20 m³ shell, 3.5 m³ of gas, DN400 differential connection (Kout 2 / Kin 10), line minimum +4.3 m and maximum 119.2 m — the transient model holds +3.0 m for any gas setting from 3.22 m³ up to 5.21 m³, the lower end only 0.28 m³ below the design setting. Past 5.21 m³ the gas fills the shell, the vessel empties and the minimum falls below the criterion, so the window is closed at both ends. Between the design setting and that ceiling, the limit is the water reserve. The design setting expands to 16.17 m³ and leaves 3.83 m³ of water, 19 % of the shell; keeping 15 % caps the gas at 3.85 m³, 10 % at 4.28 m³, and at 5.21 m³ no water is left. A full 20 % would need 3.43 m³, just under the design setting. So the band is a few tenths of a cubic metre either side: choose the reserve to protect, then set the compressor-start level and the low-gas and high-gas alarms with the transmitter accuracy and the strapping table in front of you. How the connection shapes that envelope is in the differential orifice article.

A drained vessel is the easier case. Drain a 19.1 m³ shell with its vent open and it fills with atmospheric air that, closed and brought to the steady HGL, occupies 2.07 m³ — two-thirds of the duty. The compressor supplies only the remaining 1.01 m³ (9.3 m³ of free air).

7 · Interactive: keeping the air in

The compressor duty is a free-air calculation: the gas at the steady pressure, scaled to atmospheric, divided by the recharge time you allow.

\[ V_{free} = V_0\,\frac{P_0}{P_{atm}}, \qquad FAD = \frac{V_{free}}{60\,t_{recharge}} \quad \text{(m}^3\text{/min of free air, } t \text{ in hours)} \]
Compressor free air delivery against the time allowed for a full recharge
Free air: volume at atmospheric pressure (10.33 m), taken as the compressor inlet condition; temperature correction ignored. The daily top-up is an illustrative percentage of the charge, not a dissolution rate: take that from the supplier or from site records.
The charge the compressor must rebuild when the vessel has lost all its air.
Higher pressure packs more free air into the same gas volume.
An operating decision: how long the station can wait before it is protected again.
Illustrative only. The real rate depends on pressure, temperature and water surface.
Free air per full recharge
28.4 m³
Free air delivery
0.237 m³/min
Daily top-up (illustrative)
0.28 m³/day
Run time for it (illustrative)
1.2 min/day

Recharging the reference charge of 28.4 m³ of free air in two hours takes 0.237 m³/min of free air delivery; one hour doubles it to 0.474, four hours halves it to 0.118. That is an operating decision dressed as a mechanical one: how long may the station wait, unprotected, after the vessel has lost its air? The top-up slider is deliberately illustrative; whatever the real dissolution rate, the recharge sizes the machine.

8 · Interactive: when the gas setting drifts

What the level controls protect against, run through the transient model on the 20 m³ reference vessel. Each option is the gas volume the controls happened to be holding when the power failed.

Head at the pump after a trip, for different gas settings in the 20 m³ vessel
Transient model, reference system, all pumps trip at t = 0. Grey dashed: the 3.5 m³ design setting, shown when another setting is selected. Line minimum and maximum are for the whole line over 150 s. Where the vessel empties, vapour forms at the pump end and the maximum is given across both cavity models. Amber where the setting misses +3.0 m, or holds it with less water at maximum expansion than the design setting.
Too little gas is a compressor that has fallen behind. Too much is a level transmitter reading high, so the controls keep adding air.
Gas setting
3.50 m³ · 17.5 % of shell
Line minimum, whole line
+4.3 m
Line maximum, whole line
119.2 m
Gas at maximum expansion
16.17 of 20 m³, 3.83 m³ water left
Status
holds +3.0 m

At the design setting the line minimum is +4.3 m and the gas expands to 16.17 m³, leaving 3.83 m³ of water. Select 2.00 m³, a compressor that has fallen behind dissolution, and the line minimum drops to −3.8 m: below the criterion, still clear of vapour. Select 4.50 m³ and the line minimum improves to +7.2 m, but only 1.52 m³ of water is left at maximum expansion. Select 6.00 m³, a transmitter reading high, and the vessel empties: vapour forms at the pump end and a real vessel would pass air into the main (see air admission). The later maximum of about 96 m comes from the returning column compressing the gas, about a minute after the cavity has closed, which is why both cavity models agree. The failures sit either side of the design setting, so an air-over-water vessel needs both a low-gas and a high-gas alarm, and both drift cases belong in the HAMMER study.

9 · Bladder and diaphragm details

Checking the pre-charge

In service the bladder transmits the line pressure to the gas, so a gauge on the gas valve reads water pressure, not pre-charge. The pre-charge can only be measured with the water side isolated and drained to zero pressure. That takes an isolation valve, a drain, a period without protection or with a second vessel, and a low-range gauge that reads to a few hundredths of a bar (the setting is 0.16 bar g) — and the reading is at whatever the ambient temperature is.

Temperature

The pre-charge is a fixed mass of gas, so its pressure follows absolute temperature. Set at 20 °C, a sun-exposed vessel at 45 °C reads 318.15/293.15 = 8.5 % higher:

A pre-charge of 12.00 m abs set at 20 °C, read at other gas temperatures
Gas temperature at the checkAbsolute temperature ratioReads (m abs)Reads (bar g)Fraction of Pmin
0 °C0.93211.180.080.84
20 °C (setting)1.00012.000.160.90
35 °C1.05112.610.220.95
45 °C1.08513.020.260.98

The trap is the correction, not the heat. A technician who finds 13.02 m abs on a hot afternoon and bleeds the vessel back to the specified 12.00 has removed gas: back at 20 °C the pre-charge is 11.06 m abs and the vessel carries 2.84 m³ at the steady HGL instead of 3.08. In the transient model the line minimum moves from +3.0 m to +1.8 m. Put the reference temperature on the nameplate and a correction table in the O&M manual.

The membrane

The bladder or diaphragm is the part that wears: it flexes on every start and trip, sits permanently in the water, and must be approved for potable use under NSF/ANSI/CAN 61 [8] or the local equivalent. Specify replacement access (manway or flanged head, lifting points, headroom), the supplier's orientation, and a spare. Check the squeeze as well: the 12.00 m abs pre-charge is compressed 7.9:1 into 12.6 % of the shell in steady service, and 11.8:1 at the 130.9 m transient peak. Confirm with the supplier the pressure ratio and smallest gas fraction the membrane allows; a low pre-charge on a high-head main can exceed them. A ruptured membrane turns the vessel into an uncontrolled air-over-water vessel, its gas dissolving with no level instrument to show it. A membrane replaced and returned to service with atmospheric air instead of the specified pre-charge holds 2.65 m³ at the steady HGL, and the transient model puts the line minimum at +0.7 m: 1.67 m of forgotten pre-charge costs 2.3 m on the line.

The vessel itself

Every type is a pressure vessel designed, fabricated and inspected to EN 13445 or ASME Section VIII Division 1, within the Pressure Equipment Directive where it applies [9]; in-service inspection intervals come from national pressure-equipment regulations and the owner's inspection scheme, not from the surge study. The design pressure must cover the highest transient head at the vessel, and the line's design pressures should be checked in the EN 805 sense of maximum design pressure including surge [10]. Provide isolation and a bypass, and write down what the station may do while the vessel is out: on the reference main a trip then takes the line to vapour, with a collapse peak above PN16 (see surge risk). A vertical shell gives the level transmitter more travel per cubic metre; a horizontal one saves height.

10 · Selection by site and duty

No single criterion decides the type, and the weights depend on the site. The table gives our scores on a 1–5 scale, 5 favouring the type. They are engineering judgement, not data: re-score them for your project.

Judgement scores used in the selection figure (5 = favours the type)
CriterionAir-over-waterBladderDiaphragmReason
Shell volume for the duty53319.1 m³ against 23.2–28.4 m³ on the reference duty
No auxiliary plant155Compressor, level instruments, vent, controls and power, against none
Holds its gas without attention244Dissolved air needs top-up; a membrane separates gas from water, and losses show up at pre-charge checks
Faults visible in service422The level instrument shows lost gas in service; a lost pre-charge or torn membrane stays hidden until the next check
Very large volumes521A plain shell is limited by fabrication and transport; a membrane also by its manufacture; diaphragms usually suit smaller volumes
Remote or unmanned site244Compressors and instruments need attention and power; a membrane vessel needs periodic checks

Water quality is pass or fail rather than scored: wetted materials need potable approval [8], and compressor air must be oil-free or filtered. Pressure-vessel inspection applies to every type; bladders and diaphragms add membrane replacement.

11 · Interactive: weighted selection

Move the weights to describe your site. Each bar is the weighted average of the table's scores, scaled to 100 and split by criterion.

Weighted selection score by vessel type
Scores 1–5 from the table above (engineering judgement, not data). Score = 20 × Σ(weight × score) / Σ weight.
Space, foundations, crane and vessel cost.
Compressor, instruments, controls and their power.
Dissolution, top-up and routine checks.
Whether lost protection shows before a trip finds it.
How much the duty pushes toward the largest shells.
How rarely anyone is there to look after it.
Air-over-water
73 / 100
Bladder
60 / 100
Diaphragm
56 / 100
Leads
air-over-water

The defaults describe the reference system, a large main with a staffed pump station, where shell volume, scale and visible faults matter most: air-over-water scores 73, a bladder 60, a diaphragm 56. Now describe a small unmanned booster: shell volume 2, no auxiliary plant 5, holds its gas 4, faults visible 3, large volumes 1, remote site 5. The order reverses — bladder 75, diaphragm 74, air-over-water 50 — and the shell penalty becomes a price worth paying on a site nobody visits every week. The matrix does not make the decision; it makes the reasons explicit enough to argue about. How the vessel compares with other devices on the same main is in Choosing surge protection on one pipeline.

12 · Setting it up in Bentley HAMMER

The vessel type changes only a few properties of the Hydropneumatic Tank element, and those are where the pre-charge mistakes happen [11]. Field names differ slightly between HAMMER versions. The general workflow is in the HAMMER transient workflow and HAMMER transient tips.

13 · Design checklist

In short The gas duty does not care which vessel you buy. Air-over-water carries it in 19.1 m³, at the price of a compressor and level controls; on the site's 20 m³ reference vessel the design gas setting is only 0.28 m³ above the loss of +3.0 m, and the water reserve limits it from above. A bladder or diaphragm vessel needs 23.2–28.4 m³ at any pre-charge between 0.95 of the minimum and atmospheric, because its shell is set by isothermal charging from a pre-charge below the minimum pressure — here under 0.29 bar gauge, invisible in service and moving with temperature. Choose by pressure ratio, site and who will maintain it; then model each type's own failures in HAMMER.
Surge protection design series
  1. Wave speed: the number that sets the surge
  2. The differential orifice: empty freely, refill slowly
  3. Bladder, diaphragm or air-over-water vessel
  4. One-way surge tanks at the knee
  5. Surge relief valves: what a valve at the pump can protect
  6. Pump inertia and the flywheel
  7. Choosing surge protection on one pipeline
The sizing method itself is in Sizing the Hydropneumatic Surge Vessel.

References & standards

  1. Wylie, E.B. & Streeter, V.L. Fluid Transients in Systems. Prentice Hall, 1993 — method of characteristics, the air vessel boundary with a polytropic gas law, and column separation.
  2. ISO 2531 Ductile iron pipes, fittings, accessories and their joints for water applications — the DN800 K9 pipe of the reference system.
  3. Bergant, A., Simpson, A.R. & Tijsseling, A.S. “Water hammer with column separation: a historical review.” Journal of Fluids and Structures, 22(2), 2006 — discrete vapour and gas cavity models, and why collapse peaks depend on the cavity model.
  4. Chaudhry, M.H. Applied Hydraulic Transients, 3rd ed. Springer, 2014 — air chambers, and the gas law exponent between the isothermal and adiabatic limits.
  5. Thorley, A.R.D. Fluid Transients in Pipeline Systems, 2nd ed. Professional Engineering Publishing, 2004 — surge control devices, including gas-charged vessels of different types and their practical requirements.
  6. Boulos, P.F., Karney, B.W., Wood, D.J. & Lingireddy, S. “Hydraulic transient guidelines for protecting water distribution systems.” Journal AWWA, 97(5), 2005 — hydropneumatic tanks among the protection strategies for water systems, and design considerations for their use.
  7. Stephenson, D. “Simple guide for design of air vessels for water hammer protection of pumping lines.” Journal of Hydraulic Engineering (ASCE), 128(8), 2002 — closed-form first estimates of air vessel size, checked by transient analysis.
  8. NSF/ANSI/CAN 61 Drinking Water System Components — Health Effects — approval of membranes, linings and other wetted materials for drinking water.
  9. EN 13445 Unfired pressure vessels; ASME Boiler and Pressure Vessel Code, Section VIII, Division 1; Pressure Equipment Directive 2014/68/EU — design, fabrication and inspection of the vessel shell.
  10. EN 805 Water supply — Requirements for systems and components outside buildings — design pressures of the pipeline, including the surge allowance in the maximum design pressure.
  11. Bentley Systems. OpenFlows HAMMER product documentation and help — the Hydropneumatic Tank element (bladder option, preset gas pressure, initial gas volume, gas law exponent, ratio of losses), transient run options and the Transient Results Viewer.
#SurgeVessel #HydropneumaticTank #BladderVessel #DiaphragmVessel #AirOverWater #SurgeProtection #WaterHammer #HydraulicTransients #PreChargePressure #PolytropicExpansion #GasLaw #AirCompressor #LevelControl #DissolvedAir #PumpTrip #PowerFailure #ColumnSeparation #TransmissionMain #DuctileIron #PumpingStation #BentleyHAMMER #OpenFlowsHAMMER #TransientAnalysis #PressureVessel #EquipmentSelection #DesignChecklist #WaterEngineering #PipelineDesign