Introduction

The hydropneumatic surge vessel is one of the most effective devices for protecting a water transmission main against water hammer. It acts as a local pressure reservoir at the pump station: when the pumps trip it feeds water into the main to hold the pressure up, and when the water column swings back it takes that water in again against a cushion of compressed gas.

Updated September 2026. An earlier version of this article gave the steady gas pressure as 1.84 bar abs; 85.0 m of head plus atmospheric pressure is 9.35 bar abs. Rechecked at the correct pressure with a transient model that includes column separation, the 8.0 m³ vessel with 4.0 m³ of gas specified earlier empties during a pump trip, so the sizing, the tables, the figures and the specification have been recalculated. The results tables are now from that model, and the steps to reproduce them in Bentley HAMMER are included.

Sizing is where it goes wrong, usually quietly. The gas law has to be worked in absolute pressure; the vessel has to be checked with a transient model that can show the line separating; and the pipe between vessel and main is part of the design, not a fitting. Below I walk through the whole workflow on a 12 km DN800 ductile iron main, from the unprotected baseline to the set-up in Bentley HAMMER. The answer on this line is a 20 m³ vessel carrying 3.5 m³ of air behind a differential DN400 connection, which holds the whole line at or above +4.3 m and limits the maximum to 119.2 m against a 136 m allowable.


1. How the Surge Vessel Works

The surge vessel is a closed pressure vessel, partly filled with water and partly with compressed gas, connected to the main on the pump station discharge header. In the air-over-water vessel sized here the gas is compressed air in direct contact with the water, topped up by a compressor and held at a set water level by level control [1]. When the pumps trip:

The vessel converts the transient rather than removing it. A sharp water hammer event becomes a slow oscillation of the whole water column against a gas spring, and a model has to run long enough to see that oscillation come back to the vessel (section 6).

2. The Governing Equations

Two relations carry the design. The first is the polytropic gas law. It must be written in absolute pressure, heads measured from vacuum, not from atmosphere:

Habs · Vn = H₀,abs · V₀n = constant
Habs = gauge pressure head at the vessel + 10.33 m  |  V = gas volume (m³)  |  n = 1.2, between isothermal (1.0) and adiabatic (1.4) behaviour of the gas
Water delivered = Vmax − V₀ = V₀ · [ (H₀,abs / Hmin,abs)1/n − 1 ]
For a given volume of water the vessel must deliver, this gives the gas volume needed at steady state before the pressure at the vessel falls to Hmin.

The second relation describes the water column the vessel is feeding. Treat the main as a rigid column (incompressible water in a rigid pipe) and the flow Q leaving a vessel at the pump obeys:

(L / gA) · dQ/dt = Hv − Hres − R·Q|Q|   |   dV/dt = Q
L = 12,000 m  |  A = 0.503 m²  |  Hv = gauge head at the vessel, from the gas law  |  Hres = 44.8 m at the delivery reservoir  |  R = 40.2 / 0.70² = 82.0 s²/m⁵ (steady friction)

Together these form a mass-oscillation model: it follows the column slowing, stopping and reversing against the gas spring, and gives a quick first estimate of the gas volume. It cannot see pressure waves along the line, the pressure away from the vessel, or the line separating at vapour pressure (the things that decide whether a vessel works), so the estimate is a starting point and nothing more [2][3].


3. System Description

Reference system: design input
ParameterValueNotes
Pipeline length12,000 mSingle main, flat profile at datum elevation
Pipe diameterDN 800 mmDuctile iron, class K9 [4]
Design flow rate2,520 m³/h (0.70 m³/s)All duty pumps running
Design velocity1.39 m/sQ / A
Wave speed1,050 m/sDesign value adopted for the example (section 9)
HGL at pump discharge85.0 mSteady state; 44.8 m at the delivery reservoir
Pipe class ratingPN 16 (16 bar, about 163 m)Allowable 136 m, project criterion
Minimum allowable pressure+3.0 m gaugeAnywhere on the line; vapour limit −9.8 m
Gas law exponent (n)1.2Design value for air in contact with water (judgement); 1.0 and 1.4 checked in section 8
Wave return time 2L/a22.9 s24,000 / 1,050
Joukowsky head a·v/g149.1 mFull flow stopped instantly
Load casePump tripAll pumps at once (power failure)

Because the profile is flat at datum elevation, head and pressure head are the same number throughout this example; on a real profile, subtract the pipe elevation from the head before comparing it with either limit. Both limits are criteria for this example, not rules. Many owners accept a sub-atmospheric minimum instead, commonly around −3 m, where the pipe, joints and air valves suit it; section 8 shows what that does to this vessel. Before adopting any minimum, check it against the project specification, the owner’s or utility’s standards and the manufacturers’ ratings for the pipe, joints, gaskets, valves and air valves, and state it with its source in the design basis. On a project they come from the pipe standard, the owner's requirements and the design pressure terms of EN 805, which treats surge as part of the maximum design pressure [5]; AWWA M11 discusses the same combination of working and surge pressure for large mains [6].

How the numbers were produced. Every transient result below comes from a method-of-characteristics model [2] with a vapour cavity model, cross-checked with a gas cavity model [7] and an independent second code: 120 reaches, 150 s runs, n = 1.2, separate outflow and inflow losses on the vessel connection, and an instantaneous pump stop behind ideal check valves. That load case is conservative for the downsurge and the vessel's gas demand, but it leaves out check valve slam, and real pump inertia softens the first downsurge (see pump inertia and the flywheel). These are not Bentley HAMMER output: they are a reproducible example, and a project needs its own analysis in HAMMER, or an equivalent program, on the real profile (section 9).

4. Baseline Simulation: No Protection

Before sizing any protection device, run the unprotected case: it shows how severe the transient is and where on the profile the problem sits.

Transient model: unprotected pump trip
LocationSteady-state (m)Max transient (m)Min transient (m)Status
0 m: Pump discharge85.0165–190−9.8 (vapour)FAIL
6,000 m: Midpoint64.9150–160−9.8 (vapour)FAIL
Without protection the pressure at the pump falls to vapour as soon as the pumps stop, and the minimum envelope sits at vapour along practically the whole 12 km: the column separates. When the vapour cavities collapse, the pressure at the pump reaches 165 to 190 m, above the 136 m allowable and at or above the PN 16 rating (about 163 m) in both cavity models, and the maximum exceeds 136 m over at least 11 km of the line.

Why the maximum is given as a range

Once a line separates, the spike when the column rejoins depends on how the cavity is represented: a pocket of vapour at a computing node, or a small distributed gas content [7]. In the runs for this article and the surge protection series, the gas cavity representation puts collapse-driven peaks between 18 % lower and 10 % higher than the vapour cavity one, so the table gives the span between them. Do not design a line to survive a collapse peak, and do not read a single collapse peak from any program as a precise number. Protect the downsurge so the line never separates; then the results are firm again, and every protected result below is quoted to 0.1 m.

Figure 1. Unprotected pump trip: pressure-head envelopes along the main (method-of-characteristics model; flat profile at datum, so head and pressure head coincide). The shaded band spans the maximum from the vapour cavity and gas cavity models; the minimum is at vapour almost everywhere. Tooltips round collapse-governed values to 5 m.


5. Surge Vessel Sizing: Step-by-Step

1Steady gas pressure

The gas in an air-over-water vessel sits at the line pressure at the vessel. With the vessel on the pump discharge header, and the pipe and the vessel water surface taken at datum so that the 85.0 m HGL is also the pressure head:

P₀ = (85.0 + 10.33) / 10.20 = 9.35 bar abs
95.33 m absolute head  |  8.33 bar gauge  |  10.20 m of water per bar

For this type of vessel the gas pressure is not a setting: the compressor supplies air, the level control holds the water level, and the pressure follows the line. The designer chooses the gas volume, held in service by the level set point. Pre-charge belongs to bladder and diaphragm vessels, where the gas is sealed in before the vessel sees the line. See the pre-charge pressure of the surge vessel and bladder, diaphragm or air-over-water vessel.

2Allowable pressure limits

Hmax = 136 m (project allowable on a PN 16 main)  |  Hmin = +3.0 m gauge. Both are pressure heads, and both apply everywhere on the line, not only at the vessel: as the iteration shows, the minimum usually occurs kilometres away from it.

3First estimate: the rigid column

Integrate the rigid-column pair from section 2, with friction, and search for the smallest steady gas volume that keeps the vessel above +3.0 m. The integration gives the water the vessel has to deliver, 13.42 m³; the expansion ratio in absolute terms then fixes the gas:

(95.33 / 13.33)1/1.2 = 5.152   →   V₀ = 13.42 / (5.152 − 1) = 3.23 m³, expanding to 16.65 m³
Expansion ratio Vmax / V₀ = 5.152  |  Shell = 16.65 / 0.8 = 20.8 m³ with a 20 % water reserve at maximum expansion

A spreadsheet does this in minutes and tells you whether you are looking for 2 m³ or 20 m³; published simplified guides for air vessels on pumping lines serve the same purpose [8]. Neither can tell you where on the line the minimum falls, or whether the line separates.

4Transient iteration

Now the transient model. First, with a nearly loss-free DN400 connection (K 0.5) and no limit on the shell, sweep the gas volume to see what the line itself asks for:

Transient model: gas volume sweep, free DN400 connection
Gas at steady state (m³)Shell for 20 % reserve (m³)Line minimum (m)Minimum at (km)Line maximum (m)Result
1.514.4−6.86.0143.7FAIL
2.015.8−3.25.4131.8FAIL
2.517.2−0.15.0131.2FAIL
3.0819.1+3.04.6130.9LIMIT
3.520.4+4.51.4127.5PASS
4.021.9+5.80.7121.4PASS

The line needs 3.08 m³ of gas at the steady HGL, expanding to 15.30 m³: a 19.1 m³ shell with a 20 % water reserve. With too little gas the minimum sits 5 to 6 km out, in the middle of the line; only with generous gas does it move back towards the station. Read the minimum from the whole profile, never from the vessel node alone.

The shell is then fixed at a round 20 m³ and the connection made differential (outflow K 2, inflow K 10 on DN400, for reasons given in section 7), and the gas volume is iterated again:

Transient model: 20 m³ shell, differential DN400 connection
RunGas (m³)Line minimum (m)Line maximum (m)Largest gas volume (m³)Result
Run 12.0−3.8126.412.53FAIL
Run 22.5−0.7124.313.65FAIL
Run 33.0+1.9123.514.91FAIL
Run 4 (selected)3.5+4.3119.216.17PASS ✓
Run 4, free connection3.5+4.5127.516.36PASS

I selected Run 4: 3.5 m³ of gas in a 20 m³ shell. It clears +3.0 m by 1.3 m (Run 3 misses by 1.1 m) and stays about 17 m under the allowable. The set point has little room either way. Below about 3.22 m³ of gas the line falls under +3.0 m. More gas improves the pressures but uses up the water reserve, until at about 5.2 m³ the gas fills the whole 20 m³ at maximum expansion. Holding the 20 % reserve of section 7.4 caps the gas at about 3.43 m³ (a 15 % reserve, at about 3.85 m³), so 3.5 m³ already sits just past the 20 % line, and the level-control band has to be specified in tenths of a cubic metre.

Estimate and model agree here, partly by coincidence. The gas volumes agree within 5 % (3.23 m³ from the rigid column, 3.08 m³ from the model with the free connection), but the rigid column draws about 10 % more water (13.42 against 12.22 m³). It also holds +3.0 m at the vessel, while the model reaches +3.0 m 4.6 km out with +3.6 m at the vessel. On a line with high points, or once any part of it separates, the rigid column has nothing to say: the transient model decides.

6. Final Results: 20 m³ Vessel with 3.5 m³ of Gas

Transient model: protected pump trip (20 m³ shell, 3.5 m³ gas)
LocationSteady-state (m)Max transient (m)Min transient (m)Status
0 m: Pump discharge85.0119.2+4.9OK ✓
4,300 m: Line minimum70.698.9+4.3OK ✓
6,000 m: Midpoint64.987.1+4.9OK ✓

During the trip the gas volume ranges from 2.71 m³ at the peak to 16.17 m³ at maximum expansion, leaving 3.83 m³ of water (19 % of the shell) in the vessel at its lowest. No column separation occurs anywhere on the line, so these results are firm to 0.1 m.

95.33 × (3.5 / 16.17)1.2 − 10.33 = +4.9 m   |   95.33 × (3.5 / 2.71)1.2 − 10.33 = 119.3 m
Gas-law check against the model: +4.9 m minimum and 119.2 m maximum at the vessel. If a model fails a check like this, suspect the vessel data before trusting the envelope.

Figure 2: Pressure-head envelopes along the main, unprotected (vapour cavity model) and with the 20 m³ vessel, 3.5 m³ of gas and a differential DN400 connection (method-of-characteristics model). Switch to the minimum detail to read the protected minimum against +3.0 m.

Figure 3 shows why run duration matters. With the vessel in place the pressure at the pump stays below its steady value for the first 90 s, and the 119.2 m peak arrives about 100 s after the trip, on the return swing; a run stopped at 60 s would never see it. Switch to the smaller gas volumes to see the downsurge deepen and the peak come earlier and higher; the readout gives the line minimum and where it falls.

Line minimum +4.3 m at 4.3 km · at the pump +4.9 m · maximum 119.2 m · largest gas volume 16.17 m³ · PASS

Figure 3: Pressure head at the pump discharge after the trip, unprotected and with the vessel (method-of-characteristics model, 150 s run); gas volume on the right axis for the selected design. The unprotected trace is from the vapour cavity model: its spikes are collapse peaks and indicative only, 165 to 190 m at the pump across the two cavity models.


7. Critical Design Parameters Often Overlooked

7.1 Gas pressure and absolute units

The gas law works only in absolute pressure. Take the water the line needs from the vessel in the free-connection sizing (15.30 − 3.08 = 12.22 m³) and back-calculate the steady gas volume with the second equation of section 2, once properly and once with gauge heads:

Closed-form check: gas needed to deliver 12.22 m³ of water
Heads usedExpansion ratio (H₀ / Hmin)1/nGas at steady state (m³)
Absolute: 95.33 / 13.33 m5.1522.94
Gauge: 85.0 / 3.0 m16.230.80: 3.7 times too small

With gauge heads the expansion ratio comes out more than three times too large, each cubic metre of gas appears to deliver far more water than it can, and the vessel comes out 3.7 times too small. The absolute closed form gives 2.94 m³ against the model's 3.08 m³ because the model reaches +3.0 m out on the line; at the vessel it bottoms out at about +3.6 m.

Use the pressure head at the vessel (the HGL minus the elevation of the vessel water surface) plus 10.33 m for absolute head, and check the unit of every pressure field you enter or read: gauge or absolute, metres or bar. A vessel sized on gauge heads looks perfectly reasonable on paper.

7.2 Connection pipe diameter

The connection has to pass the vessel's outflow at the moment the downsurge needs it. Keeping the same fittings (K 2 out, K 10 in) and the same 3.5 m³ of gas, only the bore changes:

Transient model: connection size, 20 m³ shell, 3.5 m³ gas
ConnectionLine minimum (m)Line maximum (m)Largest gas volume (m³)Result
DN400+4.3119.216.17PASS
DN300+2.5104.615.69FAIL (minimum)
DN250−0.389.714.99FAIL (minimum)

At a given flow the head loss through the same fittings scales with (400/D)4: 3.2 times at DN300, 6.6 times at DN250. Less water leaves, the downsurge goes deeper and the minimum fails, while the maximum improves because the same loss brakes the return swing. That is the trap: judged on the maximum alone, DN250 looks like the better design. Rules of thumb that set the connection as a fixed fraction of the main (DN250 on this DN800 line) do not survive the check. Size the connection from the transient model, on the minimum first.

7.3 Differential orifice

The connection can do both jobs if its loss differs with direction: free outflow, so the vessel supports the downsurge, and throttled inflow, so the return swing is braked. On this vessel a DN400 connection with K ≈ 2 out and K ≈ 10 in lowers the maximum from 127.5 m with a free connection to 119.2 m, while the minimum barely moves (+4.5 m to +4.3 m). The same restriction both ways lowers the maximum further, to 103.1 m with K 25, but it throttles the outflow too and sends the line to −4.5 m. In practice the throttle is an orifice plate that the outflow bypasses; by the Idelchik formula for a thin sharp-edged orifice [9], a plate adding K 8 to the K 2 fittings on DN400 has a bore of about 254 mm. See the differential orifice: empty freely, refill slowly.

7.4 Minimum water reserve

At maximum expansion the vessel must still hold water, or air goes into the main, and air in a pressurised transmission main is a problem of its own, whatever the air valves on the line are sized for [10]. In my practice I size to leave about 20 % of the shell as water at maximum expansion; that is engineering judgement, not a code requirement. This design leaves 3.83 m³, 19 % of the shell, at n = 1.2. I accept that because the load case is an instantaneous pump stop, which in my judgement draws harder on the vessel than a real pump run-down. It is not a comfortable margin: at n = 1.0 the same set point leaves only 2.25 m³ (11 %), as section 8 shows.

The reserve also caps the gas set point. In the same 20 m³ shell, 4.5 m³ of gas leaves only 1.52 m³ of water at maximum expansion, and with 6.0 m³ the vessel empties during the trip and the line falls to vapour. Set the low-level alarm and trip so that the vessel is never left in service with less water than the design trip draws; see air admission in transmission networks for what air does once it is in the line.

7.5 Vessel location

The vessel works on the flow leaving the pumps, so it belongs on the discharge header, downstream of the pump check valves and as close to the pumps as the layout allows: in my practice inside or immediately beside the station. On this flat line the steady pressure head, and with it the gas pressure, changes little over a short distance (84.8 m at 50 m down the line, 83.3 m at 500 m), but any length of main between the pumps and the vessel changes the answer. Model the vessel where it will actually be connected, at its real elevation.


8. Sensitivity Analysis

How far does the vessel move when the inputs move? Each case repeats the free-connection sizing of step 4 (the gas needed for +3.0 m anywhere on the line, and the shell with a 20 % water reserve), changing one input at a time. The base case is 3.08 m³ of gas in a 19.1 m³ shell.

Transient model: required vessel, one change at a time
Change from the base caseGas (m³)Shell (m³)Change in shellSensitivity
Base case3.0819.1––
Minimum criterion +5.0 m (tighter)3.6821.0+10 %Medium
Minimum criterion +1.0 m (looser)2.7017.8−7 %Medium
Minimum criterion −3.0 m (sub-atmospheric, common practice)2.0315.9−17 %High
Line doubled to 24 km (same flow and end heads)6.1638.2+100 %High
Wave speed 700 m/s3.1919.10 %Low
Wave speed 450 m/s (GRP-type pipe)1.9912.7−34 %High
Wave speed 300 m/s (PE-type pipe)nonenoneNo vessel for this criterionHigh
Gas law exponent n = 1.02.2218.1−5 %Medium
Gas law exponent n = 1.44.0620.5+7 %Medium
DN250 connection, same loss coefficient (K 0.5)3.3319.5+2 %Low
Differential DN400 connection, 1:53.2219.3+1 %Low

9. Setting It Up in Bentley HAMMER

The figures above come from an independent transient model, not from HAMMER; this is how to reproduce the design in Bentley HAMMER [11]. Field names differ slightly between HAMMER versions; the intent of each step does not. For the wider workflow see computing a transient simulation in HAMMER and tips for interesting transient results.

  1. Build and check the steady state. Pump, Pipe and Reservoir on the real profile. To reproduce this example, enter the adopted 1,050 m/s in each Pipe's wave speed field. On a project, use the Wave Speed Calculator (pipe material, wall thickness, Young's modulus, Poisson's ratio, restraint condition); for DN800 K9 it gives about 1,080 to 1,117 m/s depending on restraint. Confirm 85.0 m at the discharge and 44.8 m at the delivery reservoir before any transient run.
  2. Define the pump trip. Trip all pumps at time zero, with the check valve on each pump. The numbers here use an instantaneous stop; repeat with the real pump and motor inertia and check valve closure.
  3. Set the transient run options. Run duration of at least 150 s on this line (the peak at the vessel arrives about 100 s after the trip), and longer on a longer line; the computed time step; a small wave speed adjustment tolerance; vapour pressure and column separation on; one friction method throughout.
  4. Run the unprotected case and read the envelopes. If the line reaches vapour, read its maximum as a range (section 4).
  5. Add a Hydropneumatic Tank at the discharge node, downstream of the pump check valves, at its true elevation. Leave the bladder option (“has bladder”) off for an air-over-water vessel; the preset gas pressure belongs with that option.
  6. Enter the vessel. Tank volume 20 m³, initial gas volume 3.5 m³ at the steady HGL, gas law exponent 1.2, then repeat the run at 1.0 and 1.4 (section 8). When iterating from scratch, start the initial gas volume at the rigid-column estimate.
  7. Describe the connection. Inlet orifice diameter 400 mm (the bore the coefficients refer to), minor loss coefficient 2 for the outflow, ratio of losses 5 so that the inflow carries K 10. Run ratio 1 and ratio 5 once each: the ratio should lower the maximum and leave the minimum alone; if the minimum moves, it is acting the wrong way round.
  8. Read the envelopes. In the Transient Results Viewer, plot the profile (path) with the maximum and minimum head envelopes and the pipe elevation. The limits apply to pressure head, so check head minus elevation against 136 m and +3.0 m, and look for vapour wherever the minimum head drops to about 9.8 m below the pipe; only on a flat line at datum, like this example, can the head envelopes be read against the limits directly. Find where the minimum falls: here 4.3 km out, not at the vessel.
  9. Read the time histories at the tank: head, gas volume and flow. Repeat the gas-law check of section 6 on the peak and on the trough.
  10. Iterate and check. Iterate the gas volume, and the ratio of losses if the maximum is the problem, until both limits are met with margin; run a gas volume either side of the set point, because the level control will not hold it exactly; and confirm the largest gas volume stays below the tank volume with the water reserve intact: 16.17 of 20 m³ here. If a trial shows vapour anywhere, fix the downsurge rather than argue about the peak.

10. Final Vessel Specification

Surge vessel: final design specification
ParameterValue
Vessel typeAir-over-water (compressed air in contact with water)
Total vessel volume20 m³
Initial gas volume (V₀)3.5 m³ (17.5 % of the shell) at the steady HGL; narrow level-control band: below about 3.22 m³ the line minimum falls under +3.0 m, and more gas uses up the water reserve
Gas pressure at steady state9.35 bar abs (8.33 bar g): follows the line; not a setting
Gas law exponent (design)n = 1.2, engineering judgement; at n = 1.4 the line minimum falls to +0.3 m (section 8)
Gas volume in the design trip2.71 m³ to 16.17 m³
Water remaining at maximum expansion3.83 m³ (19 % of the shell) at n = 1.2; 2.25 m³ (11 %) at n = 1.0
Maximum transient pressure at the vessel119.2 m (11.7 bar g)
Line envelope, design tripMinimum +4.3 m at 4.3 km; maximum 119.2 m at the vessel
Gas supplyCompressed air, with compressor and automatic level control; nitrogen only if the owner specifies it (engineering judgement)
ConnectionDN400, differential: outflow K ≈ 2, inflow K ≈ 10 (orifice plate bypassed on outflow, bore ≈ 254 mm by the Idelchik formula)
Level instrumentationLow-level alarm and trip set so that the design water reserve is never drawn on in service
Vessel design pressureSet under the applicable pressure vessel code above the maximum transient at the vessel [12]
LocationPump station discharge header, downstream of the pump check valves, close to the pumps

11. Conclusion and Design Checklist

On this 12 km DN800 main the unprotected line separates along practically its whole length, with collapse peaks of 165 to 190 m. The design that meets both limits at the design exponent n = 1.2 is a 20 m³ vessel with 3.5 m³ of air behind a differential DN400 connection, holding the line between +4.3 m and 119.2 m. Its margins on the gas law exponent and on the water reserve are thin, and the owner should know that before the vessel is ordered. On your own project:

Surge protection design series
  1. Wave speed: the number that sets the surge
  2. The differential orifice: empty freely, refill slowly
  3. Bladder, diaphragm or air-over-water vessel
  4. One-way surge tanks at the knee
  5. Surge relief valves: what a valve at the pump can protect
  6. Pump inertia and the flywheel
  7. Choosing surge protection on one pipeline
Bladder pre-charge, and the gas setting of an air-over-water vessel, are in The Pre-Charge Pressure of the Surge Vessel.

References

  1. Thorley, A.R.D. (2004). Fluid Transients in Pipeline Systems, 2nd ed. Professional Engineering Publishing: surge protection devices and air vessels on pumping systems.
  2. Wylie, E.B. and Streeter, V.L. (1993). Fluid Transients in Systems. Prentice Hall: method of characteristics, air chambers, rigid-column analysis and column separation.
  3. Chaudhry, M.H. (2014). Applied Hydraulic Transients, 3rd ed. Springer: air chambers, mass oscillation and transient analysis of pumping mains.
  4. ISO 2531. Ductile iron pipes, fittings, accessories and their joints for water applications: pipe classes, including K9.
  5. EN 805. Water supply, Requirements for systems and components outside buildings: design pressure terms, including the allowance for surge.
  6. AWWA M11. Steel Pipe, A Guide for Design and Installation: working and surge pressure in the design of large transmission mains.
  7. Bergant, A., Simpson, A.R. and Tijsseling, A.S. (2006). “Water hammer with column separation: a historical review.” Journal of Fluids and Structures, 22(2): vapour and gas cavity models, and why collapse peaks depend on the model.
  8. Stephenson, D. (2002). “Simple guide for design of air vessels for water hammer protection of pumping lines.” Journal of Hydraulic Engineering (ASCE), 128(8): simplified first sizing of air vessels.
  9. Idelchik, I.E. (1996). Handbook of Hydraulic Resistance, 3rd ed. Begell House: loss coefficient of a thin sharp-edged orifice.
  10. AWWA M51. Air Valves: Air-Release, Air/Vacuum, and Combination, air valve types, sizing and location on pipelines.
  11. Bentley Systems. OpenFlows HAMMER product documentation and help: the Hydropneumatic Tank element, transient run options and the Transient Results Viewer.
  12. EN 13445 Unfired pressure vessels; ASME Boiler and Pressure Vessel Code, Section VIII, Division 1; Pressure Equipment Directive 2014/68/EU: design pressure of the vessel itself.
#SurgeAnalysis #WaterHammer #HydropneumaticVessel #SurgeVessel #AirVessel #PumpTrip #ColumnSeparation #MethodOfCharacteristics #HydraulicTransients #SurgeProtection #BentleyHAMMER #OpenFlowsHAMMER #PipelineDesign #WaterTransmission #DuctileIron #PumpStations #WaterEngineering #SaudiArabia