A transient model is a simplification of the network, and the simplifications are not neutral. On the 12 km reference main with its vessel, an offtake of 0.15 m³/s at 6 km changes the answer depending only on how it is drawn. As a fixed demand the line falls to +2.11 m and fails the +3.0 m criterion; as a pressure-dependent demand it holds +3.82 m; as a branch pipe to a tank, +5.57 m; left out altogether, +4.33 m. Add a closed 1.5 km branch to the main and the line minimum drops to +1.26 m while the dead end goes to vapour. This article shows which network details a surge model must keep, how to model demands, and what can safely be removed.
1 · Why network detail matters in a transient
A steady-state model only needs the network to carry the right flows at the right heads, so it tolerates heavy simplification. A transient model also needs the network to reflect, absorb and store pressure waves correctly [1][2]:
- Every junction reflects part of a wave, and every branch sends part of it away and back later.
- A dead end doubles the wave that reaches it and returns it to the main, delayed by twice its travel time.
- Demands respond to pressure. A real offtake, tap or leak draws less when the pressure falls, which damps a downsurge; a fixed-flow demand keeps drawing, which deepens it.
- Tanks and reservoirs on branches feed water back during a downsurge and absorb it during an upsurge.
The examples use the series' reference main: 12 km of DN800 ductile iron at a wave speed of 1,050 m/s, 0.70 m³/s entering at the pump, a delivery reservoir at 44.8 m, and the series vessel (3.5 m³ of gas, DN400 differential connection) protecting an instant pump stop [3]. The network solver is the same method-of-characteristics code with a vapour cavity model, verified against the series solver to 0.01 m.
2 · Fixed or pressure-dependent demand
The offtake at 6 km takes 0.15 m³/s, leaving 0.55 m³/s for the second half of the main. Three ways to model it are common [2][4]:
A fixed demand is the default in many models, because steady-state demands are usually entered that way. During a downsurge it keeps drawing 0.15 m³/s however low the pressure falls, so the main loses water it would in reality keep. The orifice form, sized to pass \(q_0\) at the steady pressure \(p_0\), draws less as the pressure falls and more when it rises. A real offtake to a tank is a pipe, and the tank supplies water back into the main when the main falls below it.
The three ways of modelling the same offtake give +2.11, +3.82 and +5.57 m: a fail, a narrow pass and a comfortable pass. The fixed demand is the most pessimistic, the branch to a tank the most favourable, because the tank feeds water back into the main at 6 km. The orifice demand also moves the lowest point: from 4.7 km to the pump. Leaving the offtake out (+4.33 m) is not conservative here: it overstates the margin of the fixed-demand case by 2.2 m.
The pressure-dependent demand falls from 0.15 to 0.069 m³/s as the downsurge arrives and rises to 0.18 on the return: it behaves as a small relief at the junction. The closed branch fills and empties with every reflection, and its far end goes to vapour 18 s after the trip, while the main loses 3 m of minimum.
3 · Dead ends and closed valves
A closed branch is the clearest example of a detail that skeletonisation must keep. A wave entering it reflects from the closed end with doubled amplitude and comes back to the main after \(2L_b/a\): 2.9 s for the 1.5 km branch here [1][5]. The returning wave adds to the main's own transient. In our case the closed branch, carrying no flow at all, takes the main from +4.33 to +1.26 m and its own far end to vapour. Fire mains, washout and future-connection stubs, and valves normally closed between zones are all closed branches during a transient.
4 · What can be removed, and what cannot
| Detail | Keep or remove | Why |
|---|---|---|
| Large offtakes and branches to tanks | Keep as pipes | They reflect, feed back and change the result (section 2) |
| Closed branches, dead ends, normally closed valves | Keep | They double and return the wave (section 3) |
| Small distributed demands | Lump into pressure-dependent demands at nearby nodes | Fixed demands overstate the downsurge |
| Short pipes and fittings in series | Merge, keeping travel time | They force a small time step (see time step) |
| Loops in a distribution network | Keep the main loops | A loop splits and recombines waves; a tree model can miss or exaggerate peaks |
| Devices, high points and changes of section | Always keep | They are where the answer is read |
The test of any simplification is to run the governing scenario on the detailed and the skeletonised model and compare the envelopes at the critical points [2][6]. A skeleton that changes the minimum by more than the margin describes a different system.
The spread between the five models (4.3 m on the main) is larger than the margin of the base design (1.3 m). The modelling choice decides the verdict.
5 · Setting it up in Bentley HAMMER
Field names differ slightly between versions [7].
- Start from the steady-state model and decide, branch by branch, what the transient model must keep, using the table in section 4.
- Use Skelebrator for series pipes and small branches, but lock the elements that must stay: offtakes to tanks, closed branches, devices, high points.
- Choose the demand representation for the transient: check how your version treats junction demands during a transient run, and use a pressure-dependent form (an emitter or orifice) for offtakes that really respond to pressure. Model large offtakes as pipes to their tanks.
- Keep normally closed valves as closed valves, so the branches behind them are dead ends in the transient.
- Run the governing scenario on both models, the detailed and the skeleton, and compare the envelopes at the critical points before using the skeleton for the protection design.
- Bracket the demand model: run fixed and pressure-dependent demands and report both if the verdict depends on it.
6 · Checklist
- Every large offtake modelled as a pipe to its tank, or as a pressure-dependent demand.
- Dead ends and closed valves kept, with their branches.
- Small demands lumped into pressure-dependent demands, not fixed flows.
- Skeleton checked against the detailed model on the governing scenario.
- Demand model bracketed where the verdict depends on it.
- Loops kept in distribution networks.
- Is your HAMMER run right? Time step, adjustment and run duration
- Validating a surge model with a field pump-trip test
- Sensitivity and uncertainty: bounding the result
- Pump data for a pump trip: inertia, specific speed and four-quadrant curves
- Demands, branches and dead ends in a transient model
- Reading the surge envelope against the pipe's real limits
- Transient forces on pipe supports and bends
- Booster stations in series
- Pump starts, controlled stops and drive ramps
- Filling, draining and restarting a transmission main
- Surge in wastewater force mains
- The surge study report: what to deliver and what a reviewer checks
References & standards
- Wylie, E.B. & Streeter, V.L. Fluid Transients in Systems. Prentice Hall, 1993: junctions, branches, dead ends and wave reflection in networks.
- Boulos, P.F., Karney, B.W., Wood, D.J. & Lingireddy, S. “Hydraulic transient guidelines for protecting water distribution systems.” Journal AWWA, 97(5), 2005: transients in distribution networks, demands and skeletonisation.
- Abokhatwa, M. Surge protection design series, abokhatwa.com, 2026: the reference main, its vessel and the verified MOC solver.
- Karney, B.W. & McInnis, D. “Transient analysis of water distribution systems.” Journal AWWA, 82(7), 1990: demand representation and the behaviour of networks under transients.
- Chaudhry, M.H. Applied Hydraulic Transients, 3rd ed. Springer, 2014: branching pipes and closed branches.
- Jung, B.S., Boulos, P.F. & Wood, D.J. “Effect of pipeline network skeletonization on hydraulic transient simulation.” Journal of Water Resources Planning and Management, 135(4), 2009: when skeletonisation changes transient results.
- Bentley Systems. OpenFlows HAMMER documentation: Skelebrator, junction demands, emitters, valves and transient calculation options.