Every megatall tower has a pool, and increasingly it is on the roof: an infinity edge at three hundred metres with a view. That single architectural decision transforms an ordinary building service into one of the hardest loads in the building, because evaporation depends on air movement, and at 300 m there is a great deal of it. The same 400 m² of water that evaporates quietly indoors loses 384 kg an hour on an exposed rooftop in Gulf conditions: a 262 kW latent load and 9 m³ a day of makeup water, permanently, on the highest and least accessible part of the building.

1 · Why a pool in a tower is different

2 · Interactive: evaporation, and what the wind does to it

Evaporation from a pool follows the vapour-pressure difference between the water surface and the air, enhanced by air movement[1]:

\[ \dot m = \frac{A}{Y}\,(p_w - p_a)\,(0.089 + 0.0782\,V) \]

with \(\dot m\) in kg/s, \(A\) the water surface area, \(Y\) the latent heat of vaporisation (≈2,454 kJ/kg), \(p_w\) the saturation pressure at the water temperature, \(p_a\) the actual vapour pressure of the air, and \(V\) the air velocity over the surface. The velocity term is the one that matters here: going from a still indoor 0.1 m/s to an exposed rooftop 3 m/s multiplies the coefficient by more than three.

Pool evaporation and latent load
ASHRAE evaporation correlation. Latent load = ṁ·Y; makeup water is the same mass flow. Air velocity is the value at the water surface, not the free-stream wind speed: a windbreak reduces it substantially.
Free water surface, including any spa and reflecting pools on the same system.
Leisure pools 28–30 °C; spas 36–40 °C evaporate far harder.
Ambient at the pool deck.
Dry air evaporates far more. Coastal Jeddah is humid; Riyadh is not.
Indoor still air ≈ 0.1; a screened terrace ≈ 1; an exposed roof at 300 m far more.
Evaporation
384 kg/h
Latent load
262 kW
Makeup water
9.2 m³/d
If sheltered to 0.5 m/s
104 kW
Exposure

A 400 m² rooftop pool in dry 40 °C air at 3 m/s evaporates 384 kg/h: a 262 kW load and 9.2 m³ a day of treated makeup water hauled to the top of the tower. Now drag the velocity down to 0.5 m/s, which is what a properly designed windbreak or recessed pool surround achieves: the load falls to about 104 kW, a 60 % reduction, for architecture rather than plant. That is the single highest-value intervention available, and it has to be argued at concept design because it is a form decision. A pool cover at night is the second: covering for eight hours cuts daily evaporation by roughly a third at no capital cost beyond the cover itself.

3 · Interactive: turnover, filtration and the plant

Water quality is maintained by continuously recirculating the whole volume through filtration and disinfection. The turnover period (the time to pass a volume equal to the pool through the plant) is set by code and by bather load, and it sizes everything downstream.

Circulation flow, filter area and pump duty
Flow = pool volume ÷ turnover period. Filter area = flow ÷ design filtration velocity. Pump duty from flow and the circuit head including filter, heater, strainer and any static lift to a remote plant room.
Open Pump hydraulic power as a calculator
Surface area × average depth, plus balance tank.
Public leisure pools 3–4 h; spas 10–20 min; private pools up to 8 h.
Sand filters run 25–37 m/h. Lower velocity filters better and needs more area.
Filter, heater, strainer and pipework, plus any lift to a plant room on another level.
Circulation flow
160 m³/h
In L/s
44 L/s
Filter area
6.4 m²
Pump shaft power
11.2 kW
Backwash flow
288 m³/h

A 640 m³ pool on a four-hour turnover needs 160 m³/h: 44 L/s circulating continuously, through 6.4 m² of filter, for about 11 kW of pump power running 8,760 hours a year. Two design traps sit in the readouts. The backwash flow is far larger than the circulation flow, typically 45 m/h against 25, so the backwash pipework, the waste drain and the balance tank must be sized for it, not for normal operation. And note the head slider: if the plant room is on a different level from the pool, the circuit becomes a tall open loop, the pump has to lift the water, and the pump power multiplies. Put the plant room on the same level as the pool if the architecture allows it.

4 · Water treatment, and why the balance tank matters

5 · Heating, and where the energy actually goes

For a heated pool, evaporation is typically 60–70 % of the total heat loss, more than conduction, radiation and makeup heating combined. Three consequences follow, and they are all cheap:

In a Gulf tower the more common case is the opposite: an outdoor pool that needs cooling in summer to stay comfortable, which is a genuine chilled-water load, and heating only in the short winter. Design for both and confirm which governs.

6 · Interactive: the load on the roof

Pool mass and sloshing allowance at the top of a tower
Static mass from volume; dynamic allowance as a fraction of static representing the sloshing (convective) mass excited by building sway. Indicative only: a real design needs a fluid-structure assessment.
Plan area of the pool tank.
Mean water depth across the tank.
Share of the water mass participating dynamically under building sway.
Tank, finishes and surround as a share of the water mass.
Water mass
640 t
Sloshing mass
96 t
Total dead load
896 t
Load intensity
22.0 kPa
vs office floor
7.3×

A 400 m² pool at 1.6 m mean depth is 640 tonnes of water and, with the tank and surround, close to 900 tonnes at roof level: a load intensity of 22 kPa, roughly seven times a normal office floor. It also sits at the point of maximum building sway, so a share of that water is a dynamic mass moving with the structure. Two things follow that the MEP engineer must actually do: issue the full operating mass including the balance tank to the structural engineer early, and note that a pool near the top of a tower interacts with the building's dynamics, in some towers deliberately, as a tuned sloshing damper, which is only possible if the interaction is recognised at concept rather than discovered in commissioning.

7 · Installation & execution tricks

8 · The design & installation checklist

The one-line summary A rooftop pool turns an ordinary building service into one of the tower's largest loads, because evaporation scales with air velocity and a roof at 300 m is a windy place: 400 m² of water loses 384 kg/h and 262 kW exposed, against about 104 kW sheltered. Shelter and a cover are worth more than any plant you can buy, and both are concept-stage architectural decisions. Then size the balance tank for displacement plus surge rather than as a sump, size the drain for the backwash rather than the circulation, keep the plant on the pool's own level so the circuit is not a tall open loop, and issue the 900-tonne operating mass to the structural engineer before the roof is designed rather than after.

References & standards

  1. ASHRAE Handbook, HVAC Applications, Natatoriums chapter: pool evaporation correlation, dehumidification, air distribution and heat recovery.
  2. PWTAG Swimming Pool Water: Treatment and Quality Standards for Pools and Spas, turnover periods, filtration velocities, disinfection and monitoring.
  3. BS EN 15288-1 and -2, swimming pools: safety requirements for design and for operation; and ISO 20380 for pool water treatment plant.
  4. WHO Guidelines for Safe Recreational Water Environments, Volume 2: Swimming Pools and Similar Environments.
  5. ANSI/APSP/ICC standards for public and residential pools and spas; and the International Swimming Pool and Spa Code.
  6. HSE HSG282: control of Legionella and other infectious agents in spa pool systems.
  7. CIBSE Guide G and SPATA design standards: pool hall services, balance tanks and plant sizing.
  8. Saudi Building Code SBC 701 and local health authority requirements for public pools and water features.
#SwimmingPools #Natatorium #RooftopPool #InfinityEdge #Spa #Wellness #TallBuildings #MegatallBuildings #Evaporation #LatentLoad #PoolCover #Windbreak #Turnover #Filtration #SandFilter #Backwash #BalanceTank #Disinfection #Chlorine #UV #Ozone #Chloramines #Legionella #HSG282 #PWTAG #HeatPumpDehumidifier #StructuralLoad #Sloshing #Waterproofing #Commissioning #MEP #BuildingServices